Frequency converter
FC-202P900T7E21H2TGC3XKSXXXXALB4CXXXXD0
VLT® AQUA Drive FC-202
(P900) 900 KW / 1250 HP, Three phase
525 - 690 VAC *, IP21 / Type 1
RFI Filter
Safe Stop
Graphical Loc. Cont. Panel
Coated PCB, Mains Disconnect + Fuse
Latest release std. SW.
PROFINET MCA 120, MCB-114 VLT Sensor Input
No C1 option, MCB-107 24V DC backup
Frame: F3
Other options according to Model code
Danfoss VLT® AQUA Drive is dedicated to water and wastewater applications. With a wide range of powerful sta.
Gross weight | 1017.3 kg |
Net weight | 1017 kg |
Volume | 0 l |
EAN | 5715253318509 |
Product View (Switch) | GLBL | Global (Standard) |
Product Group | FC- | VLT® AQUA Drive FC- |
Series | 202 | 202 |
Power Rating | P900 | (P900) 900 KW / 1250 HP |
Phase | T | Three phase |
Mains Voltage | 7 | 525 - 690 VAC * |
Possible rating issue | WARN01 | Possible Rating Issue: |
Enclosure | E21 | IP21 / Type 1 |
RFI Filter | H2 | RFI Filter |
Brake - Safe Stop | T | Safe Stop |
LCP | G | Graphical Loc. Cont. Panel |
Coating PCB | C | Coated PCB |
Mains Option | 3 | Mains Disconnect + Fuse |
Adaptation A | X | Standard Cable Entries |
Adaptation B | K | F Frame Common Motor Term |
Software Release | SXXX | Latest release std. SW. |
Software Language Pack | X | Standard Language Pack |
A Option | AL | PROFINET MCA 120 |
B Option | B4 | MCB-114 VLT Sensor Input |
C0 Option MCO | CX | No C0 option |
C1 Option | X | No C1 option |
C Option Software | XX | No software option |
D Option | D0 | MCB-107 24V DC backup |
Frame Size | F3 | F3 |
Typecode Part 1 | FC-202P900T7E21H2TGC | |
Typecode Part 2 | 3XKSXXXXALB4CXXXXD0 | |
Product Catalog | GLBL | Global (Standard) |
Power 150% (HO) [KW] | 800 | |
Power 110% (NO) [KW] | 900 | |
Height [mm] | 2204,0 | |
Width w/ no C options [mm] | 2000,0 | |
Depth [mm] | 606,0 | |
Depth with Option A/B [mm] | 606,0 | |
kVA | 1129 | |
Power Loss NO [W] | 12316 | |
Power Loss NO [W] | 12798 | |
Power Loss HO [W] | 10860 | |
Power Loss HO [W] | 11291 | |
Continuous Current (NO) [A] | 988 | |
Intermittent Current (NO) [A] | 1087 | |
Continuous Current (NO) [A] | 945 | |
Intermittent Current (NO) [A] | 1040 | |
Continuous Current (HO) [A] | 889 | |
Intermittent Current (HO) [A] | 1334 | |
Continuous Current (HO) [A] | 850 | |
Intermittent Current (HO) [A] | 1275 | |
Calculated Gross Weight [kg] | 1017.3 | |
Calculated Net Weight [kg] | 1017 | |
Plant from Orderline | B901 | |
Vendor | ERR01 | Cannot Determine Vendor |
Recommended Factory | ERR01 | Cannot Determine Vendor |
Modelcode01 | FC-202P900T7E21H2TGC | |
Modelcode02 | 3XKSXXXXALB4CXXXXD0 |